Technical Specs
RhinoCross® Channel

CL501CL502
Panel Size
(mm)
500 x 500500 x 500
Panel Thickness25.00 mm26.00 mm
Panel Weight9.50 kg10.00 kg
System Weight35.19 kg36.58 kg
Concentrated Load3.00 kN4.50 kN
Uniform Load8.00 kN12.00 kN
Ultimate load9.00 kN13.50 kN
  • This low-profile channel system is tested in accordance with PSA MOB PS/SPU specification

  • Panel deflection at centre edge must not exceed 2.5 mm

  • Performance to a safety factor of 3 x static load

  • Structural performance based upon a full Rhino access floors system i.e. panels & pedestals


Features
RhinoCross® Channel
  • Low-profile height adjustable 35-100mm raised floors

  • Quick connect channel system

  • Organized channels for high volume cable management

  • Save t

Download Brochures
RhinoCross® Channel
More About